AFFECT -Conc. Programmed for a concentration
- No or temperature limit or not active.
-°C/°F
LIM XXXX Enter a limit value
DIR. -Up Choice of the direction
-Down
DELAY XXXs Time before the relay is executed (in seconds)
HYST. XX% Definition of the hysteresis limit in % (10% max.). The
hysteresis operates on only one side of the limit. The
hysteresis is below the limit for the high alarm (up)
and above the limit for the low alarm (down).
RELAY -NO Relay normally open or normally closed
-NC
Limit Alarm Function
➯ LIMIT FUNCTION:
The alarm relays are activated when the comparison between the measured value and the programmed limits
meets the alarm function condition (up or down). The limits are programmed according to the following
programming variables: